Lines Matching full:temperature
10 1. "switch on" trip point: temperature above which the governor
14 2. "desired temperature" trip point: it should be higher than the
15 "switch on" trip point. This the target temperature the governor
24 temperature as the control input and power as the controlled output:
66 temperature. This is the maximum sustained power for allocation at
67 the desired maximum temperature. The actual sustained power can vary
106 constant during temperature overshoot periods (current temperature is
107 above "desired temperature" trip point). Conversely, `k_pu` is the
108 proportional term constant during temperature undershoot periods
109 (current temperature below "desired temperature" trip point).
114 available capacity at a low temperature. On the other hand, a high
116 while temperature is low, and may lead to temperature overshooting.
134 desired temperature and the current one. When the current temperature
147 - T_set is the desired temperature
148 - T is the current temperature
149 - T_on is the switch on temperature
151 When the current temperature is the switch_on temperature, the above
159 3 * `sustainable_power` to `sustainable_power` as the temperature
160 rises from the switch on temperature to the desired temperature.
168 the exact power that the governor requests. When the temperature